Temperature The temperature requirements for Electron Microscopes are not particularly high. Typically, temperatures around 26 degrees Celsius in summer and 20 degrees Celsius in winter are acceptable for comfort and energy efficiency. However, the temperature change rate is important, with common requirements being ≤0.5°C/3 minutes or ≤0.5°C/5 minutes. Good-quality central air conditioning systems can usually meet these requirements. For example, a well-known brand of split air conditioner has a four-minute cycle with temperature fluctuations of around 1 degree Celsius. Using precision air conditioning systems usually doesn't offer significant benefits in terms of price, maintenance costs, and applicability. In practice, High-precision Electron Microscopes tend to be bulky and have larger heat capacities. As long as the temperature variation inside the room is not significant, minor fluctuations within a short period are unlikely to have a noticeable impact. It's important to avoid excessively low temperatures in the electron microscope room to prevent condensation and dripping water on cooling water pipes, liquid nitrogen pipes, and Dewar flasks. For example, there was a case where an improperly placed old-fashioned spectroscopic circuit board under a liquid nitrogen Dewar flask got damaged due to condensation dripping. Regarding auxiliary equipment rooms, such as those housing circulation cooling water tanks, air compressors, uninterrupted power supply (UPS) units, and vacuum pumps, it's necessary to calculate the required capacity of the air conditioning system based on the heat dissipation provided in the equipment specifications. If the temperature in the auxiliary equipment room is too high, it can reduce the cooling efficiency of the circulation cooling water tank and increase the thermal drift of lenses. Therefore, it is recommended to keep the temperature in the auxiliary equipment room below 35 degrees Celsius throughout the year. Humidity Frozen samples have high humidity requirements, and some users prefer a relative humidity below 25%. However, extremely low humidity can lead to electrostatic discharge. To address this, the freeze-fracture preparation machine can be moved closer to the Electron Microscope to minimize the exposure time of frozen samples, thereby reducing the humidity requirements. Usually, relative humidity of below 65% is sufficient for the electron microscope room, which is a relatively low requirement that most air conditioning systems can easily meet (assuming the room door is kept closed and the time for personnel entry and exit is minimized). If it is a newly constructed building within a year, it may take some time to eliminate the building's moisture. In such cases, a dehumidifier can be added to regulate the humidity. Airflow Another consideration is the airflow from the air conditioning system. In most cases, as lo...
View MoreAs is well known, electrical equipment requires grounding for safety protection. The outer casing or exposed metal parts of various devices need to be directly connected to the earth to ensure that in the event of a short circuit or leakage, the voltage on the casing or exposed metal parts remains within a safe range for human contact (the current safety standard specifies a voltage not exceeding 24V), thus ensuring personal safety. Electron Microscopes are no exception and also require grounding for safety. In the event of a system leakage, a discharge path is provided to ensure the safety of operators or maintenance personnel. However, there is a special requirement for Electron Microscopes. The grounding wire of the electron microscope serves as the common "zero potential" reference point for various subsystems within the electron microscope (such as detectors, signal processing amplifiers, electron beam control, etc.), and the voltage must be stable at zero potential. In theory, the grounding wire is a reference point with zero voltage. However, in practice, when there is a current in the grounding circuit (this current is usually referred to as leakage current or ground current, which is the vector sum of the leakage currents generated by various electrical equipment), any grounding terminal in the grounding circuit will have a ground voltage (because the grounding resistance of any grounding wire, although small, cannot be zero, according to Ohm's law V=IR, the ground voltage V will not be zero when the leakage current I is non-zero). Although this ground voltage is usually negligible, for Electron Microscopes that often need to magnify images by tens of thousands to millions of times, the resulting impact is often significant and cannot be ignored. The fluctuation of the ground voltage directly causes artifacts similar to magnetic fields and vibration interference at the vertical edges of the scanned image, and in severe cases, it can cause image shaking. The solution to this problem is simple, which is to set up a dedicated grounding circuit specifically for the electron microscope, which is referred to as a "single earth loop." This eliminates the interference from the leakage currents of other electrical devices on the same power circuit to the Electron Microscope. Note that the grounding body, grounding wire, and grounding terminal must all be independent and not connected to any conducting body to ensure the complete independence of the grounding wire. The following common errors should be avoided: 1) Not installing a completely independent grounding body, but simply laying a grounding wire connected to a common grounding body. 2) Although there is a separate grounding body, the grounding wire or grounding terminal is connected to a common ground wire or other electrical devices. 3) Try to avoid using "equipotential terminal boxe...
View MoreFirst, let's discuss the causes of low-frequency vibrations. Repeated tests have shown that low-frequency vibrations are primarily caused by the resonances of the building. The construction specifications for industrial and civil buildings are generally similar in terms of floor height, depth, span, beam and column sections, walls, floor beams, raft slabs, etc. Although there may be some differences, particularly regarding low-frequency resonances, common characteristics can be identified. Here are some patterns observed in building vibrations: 1. Buildings with linear or point-shaped floor plans tend to exhibit larger low-frequency resonances, while those with other shapes such as T, H, L, S, or U have smaller resonances. 2. In buildings with linear floor plans, vibrations along the long axis are often more pronounced than those along the short axis. 3. In the same building, the first floor without a basement typically experiences the smallest vibrations. As the floor height increases, the vibrations worsen. The vibrations in the first floor of a building with a basement are similar to those in the second floor, and the lowest vibrations are typically observed in the lowest level of the basement. 4. Vertical vibrations are generally larger than horizontal vibrations and are independent of the floor level. 5. Thicker floor slabs result in smaller differences between vertical and horizontal vibrations. In the majority of cases, vertical vibrations are larger than horizontal vibrations. 6. Unless there is a significant vibration source, vibrations within the same floor of a building are generally consistent. This applies to locations in the middle of a room as well as those near walls, columns, or overhead beams. However, even if measurements are taken at the same location without any movement and with a few minutes interval, the values are likely to differ. Now that we know the sources and characteristics of low-frequency vibrations, we can take targeted improvement measures and make advanced assessments of the vibration conditions in certain environments. Improving low-frequency vibrations can be costly, and sometimes it is not feasible due to environmental constraints. Thus, in practical applications, it is often advantageous to choose or relocate to a better site for operating an electron microscope laboratory. Next, let's discuss the impact of low-frequency vibrations and potential solutions. Vibrations below 20 Hz have a significant disruptive effect on electron microscopes, as depicted in the following figures. Image 1 Image 2 Image 1 and Image 2 were taken by the same Scanning Electron Microscope (both at 300kx magnification). However, due to the presence of vibration interference, Image 1 has noticeable jaggedness in the horizontal direction (in segments), and the clarity and resolution of the image are significantly reduced. Image 2 is the result obtained from the same sample after eliminating the vibration interference...
View MoreThe environment of an electron microscopy lab does not directly impact the electron microscope itself but rather affects the imaging quality and overall performance of the microscope. During the operation of an electron microscope, the fine electron beam needs to travel in a high vacuum environment, covering a distance of 0.7 meters (for Scanning Electron Microscope) to over 2 meters (for Transmission Electron Microscope). Along the path, external factors such as magnetic fields, ground vibrations, noise in the air, and airflows can cause the electron beam to deviate from its intended path, leading to a degradation in imaging quality. Therefore, specific requirements need to be met for the surrounding environment. Passive low-frequency electromagnetic shielding primarily involves two methods, which differ in the shielding material used: one method uses high-permeability materials (such as steel, silicon steel, and mu-metal alloys), and the other method uses high-conductivity materials (such as copper and aluminum). Although the working principles of these two methods are different, they both achieve effective reduction of environmental magnetic fields. A. The high-permeability material method, also known as the magnetic circuit diversion method, works by enclosing a finite space (Region A) with high-permeability materials. When the environmental magnetic field strength is Ho, the magnetic reluctance of the high-permeability material is much smaller than that of air (common Q195 steel has a permeability of 4000, silicon steel ranges from 8000 to 12000, mu-metal alloys have a permeability of 24000, while air has an approximate value of 1). Applying Ohm's law, when Rs is much smaller than Ro, the magnetic field strength within the enclosed space (Region A) decreases to Hi, achieving demagnetization (see Figure 1 and Figure 2, where Ri represents the air reluctance within space A, and Rs represents the shielding material reluctance). Inside the shielding material, the magnetic domains undergo vibration and dissipate magnetic energy as heat under the action of the magnetic field. Since silicon steel and mu-metal alloys exhibit anisotropy in permeability and cannot be hammered, bent, or welded during construction (although theoretically, heat treatment can improve these properties, it is impractical for large fixed products), their effective performance is significantly reduced. However, they can still be used for supplementary or reinforcement purposes in certain special areas without hammering, bending, or welding. High-permeability materials are expensive, so they are generally not extensively used in electron microscope shielding and are only seen in a few specific areas (such as door gaps, waveguide openings, etc.). The effectiveness of the magnetic circuit diversion method is roughly linearly related to the thickness of the shielding material, which can theoretically be infinitely thin. B. The high-conduc...
View MoreThe environment of an electron microscopy lab does not directly impact the electron microscope itself but rather affects the imaging quality and overall performance. During the operation of an electron microscope, the fine electron beam needs to travel in a high vacuum environment, covering a distance of 0.7 meters (for Scanning Electron Microscope) to over 2 meters (for Transmission Electron Microscope). Along the path, external factors such as magnetic fields, ground vibrations, noise in the air, and airflows can cause the electron beam to deviate from its intended path, leading to a degradation in imaging quality. Therefore, specific requirements need to be met for the surrounding environment. The Active Low-frequency Demagnetization System, mainly composed of a detector, controller, and demagnetization coil, is a specialized device used to mitigate low-frequency electromagnetic fields from 0.001Hz to 300Hz, referred to as a Demagnetizer. Demagnetizers can be categorized into AC and DC types based on their working ranges, and some models combine both types to meet different working environments. The advantages of low-frequency demagnetizers include their small size, lightweight, space-saving design, and the ability to be installed post-construction. They are particularly suitable for environments where it is difficult to construct magnetic shielding, such as cleanrooms. Regardless of the brand, the basic working principles of demagnetizers are the same. They use a three-axis detector to detect electromagnetic interference signals, dynamically control and output anti-phase currents through a PID controller, and generate anti-phase magnetic fields with three-dimensional demagnetization coils (typically three sets of six quasi-Helmholtz rectangular coils), effectively neutralizing and canceling the magnetic field in a specific area, reducing it to a lower intensity level. The theoretical demagnetization accuracy of demagnetizers can reach 0.1m Gauss p-p, or 10 nT, and some models claim even better accuracy, but this is only achievable at the center of the detector and cannot be directly measured by other instruments due to mutual interference at close distances or the "Equipotential Surface" phenomenon at greater distances. Demagnetizers automatically adjust the demagnetization current based on changes in the environment. At times, the current can be significant. It is important to pay attention to the wiring layout when other sensitive instruments are in close proximity to avoid interference with their normal operation. For example, electron beam exposure devices have been affected by nearby operating magnetic field detectors. The power consumption of the demagnetizer controller is generally around 250W to 300W. The detector of the demagnetizer can be a combination type or an AC/DC separate type, and there is no significant difference in performance. It is generally fixed in the mid...
View MoreThe environment of an electron microscopy lab does not directly impact the electron microscope itself but rather affects the imaging quality and overall performance of the microscope. During the operation of an electron microscope, the fine electron beam needs to travel in a high vacuum environment, covering a distance of 0.7 meters (for Scanning Electron Microscope) to over 2 meters (for Transmission Electron Microscope). Along the path, external factors such as magnetic fields, ground vibrations, noise in the air, and airflows can cause the electron beam to deviate from its intended path, leading to a degradation in imaging quality. Therefore, specific requirements need to be met for the surrounding environment. As is well known, electromagnetic waves consist of alternating magnetic and electric fields. However, it is important to consider the frequency when measuring electromagnetic waves using either magnetic or electric fields. In practice, it is necessary to take the frequency into account. At very low frequencies (as the frequency tends to zero, equivalent to a DC magnetic field), the magnetic component of the electromagnetic wave becomes stronger while the electric component weakens. As the frequency increases, the electric component strengthens and the magnetic component decreases. This is a gradual transition without a distinct turning point. Generally, from zero to a few kilohertz, the magnetic field component can be well characterized, and units such as Gauss or Tesla are used to measure the field strength. Above 100 kHz, the electric field component is better measured, and the unit used for field strength is volts per meter (V/m). When dealing with a low-frequency electromagnetic environment with a strong magnetic field component, reducing the magnetic field directly is an effective approach. Next, we will focus on the practical application of shielding a low-frequency (0-300 Hz), electromagnetic field with a magnetic field strength ranging from 0.5 to 50 milligauss (peak-to-peak) in a shielded volume of 40-120 cubic meters. Considering cost-effectiveness, the shielding material used is typically low-carbon steel plate Q195 (formerly known as A3). Since the eddy current loss of a single thick material is greater than that of multiple thin layers (with the same total thickness), thicker single-layer materials are preferred unless there are specific requirements. Let's establish a mathematical model: 1. Derivation of the formula Since the energy of low-frequency electromagnetic waves is mainly composed of magnetic field energy, we can use high-permeability materials to provide magnetic bypass paths to reduce the magnetic flux density inside the shielding volume. By applying the analysis method of parallel shunt circuits, we can derive the calculation formula for the parallel shunting of magnetic flux paths. Here are some definitions: Ho: External magnetic field strength Hi: Magnetic field strength ins...
View MoreCIQTEK FIB-SEM Practical Demonstration Focused Ion Beam Scanning Electron Microscope (FIB-SEM) are essential for various applications such as defect diagnosis, repair, ion implantation, in-situ processing, mask repair, etching, integrated circuit design modification, chip device fabrication, maskless processing, nanostructure fabrication, complex nano-patterning, three-dimensional imaging and analysis of materials, ultra-sensitive surface analysis, surface modification, and transmission electron microscopy specimen preparation. CIQTEK has introduced the FIB-SEM DB550, which features an independently controllable Field Emission Scanning Electron Microscope (FE-SEM) with Focused Ion Beam (FIB) Columns. It is an elegant and versatile nanoscale analysis and specimen preparation tool, that adopts “SuperTunnel” electron optics technology, low aberration, and non-magnetic objective design with low voltage and high-resolution capability to ensure the nano-scale analysis. The ion column facilitates a Ga+ liquid metal ion source with a highly stable, high-quality ion beam to ensure nano-fabrication capability. DB550 has an integrated nano-manipulator, gas injection system, electrical anti-contamination mechanism for the objective lens, and user-friendly GUI software, facilitating an all-in-one nanoscale analysis and fabrication workstation. To showcase the outstanding performance of the DB550, CIQTEK has planned a special event called "CIQTEK FIB-SEM Practical Demonstration." This program will present videos demonstrating the broad applications of this cutting-edge equipment in fields such as materials science, the semiconductor industry, and biomedical research. Viewers will gain an understanding of the working principles of the DB550, appreciate its stunning microscale images, and explore the significant implications of this technology for scientific research and industrial development. Nano-Micropillar Specimen Preparation Nano-micropillar Specimen Preparation has been successfully achieved, demonstrating the powerful capabilities of CIQTEK Focused Ion Beam Scanning Electron Microscope in nanoscale processing and analysis. The product's performance provides precise, efficient, and multimodal testing support for customers engaged in nanomechanical testing, facilitating breakthroughs in materials research.
View MoreCIQTEK FIB-SEM Practical Demonstration Focused Ion Beam Scanning Electron Microscope (FIB-SEM) are essential for various applications such as defect diagnosis, repair, ion implantation, in-situ processing, mask repair, etching, integrated circuit design modification, chip device fabrication, maskless processing, nanostructure fabrication, complex nano-patterning, three-dimensional imaging and analysis of materials, ultra-sensitive surface analysis, surface modification, and transmission electron microscopy specimen preparation. CIQTEK has introduced the FIB-SEM DB550, which features an independently controllable Field Emission Scanning Electron Microscope (FE-SEM) with Focused Ion Beam (FIB) Columns. It is an elegant and versatile nanoscale analysis and specimen preparation tool, that adopts “SuperTunnel” electron optics technology, low aberration, and non-magnetic objective design with low voltage and high-resolution capability to ensure the nano-scale analysis. The ion column facilitates a Ga+ liquid metal ion source with a highly stable, high-quality ion beam to ensure nano-fabrication capability. DB550 has an integrated nano-manipulator, gas injection system, electrical anti-contamination mechanism for the objective lens, and user-friendly GUI software, which facilitates an all-in-one nanoscale analysis and fabrication workstation. To showcase the outstanding performance of the DB550, CIQTEK has planned a special event called "CIQTEK FIB-SEM Practical Demonstration." This program will present videos demonstrating the broad applications of this cutting-edge equipment in fields such as materials science, the semiconductor industry, and biomedical research. Viewers will gain an understanding of the working principles of the DB550, appreciate its stunning microscale images, and explore the significant implications of this technology for scientific research and industrial development. Preparation of a transmission specimen of Ferrite-martensite steel The FIB-SEM DB550 developed by CIQTEK possesses the capability to prepare transmission specimens of ferrite-martensite steel flawlessly. This capability enables researchers in the nanoscale domain to directly observe the interface characteristics, microstructural morphology, and evolution process of ferrite and martensite phases. These observations are crucial steps toward deepening the understanding of the relationship between phase transformation kinetics, microstructural organization, and mechanical properties of ferrite-martens steel.
View More